Protocole Kraft MultiPulse

Navigation:  La configuration > Alarm.ini > DB103 Alarmes redresseur >

Protocole Kraft MultiPulse

Previous pageReturn to chapter overviewNext page

Le numéro du registre correspond au numéro du redresseur.

 

DB

Reg

Bit

Fonction

103

1..80

0

Erreur de communication avec le redresseur

103

1..80

1

Sync signal missing. Probably shorted. Check cabling for sync signal.

103

1..80

2

Sync signal, bad timing. Check time parameters for all units. Periodtime must be the same on all units.

103

1..80

3

Illegal parameter. One or more parameters are in conflict. Check parameters.

103

1..80

4

High temperature warning. Unit might soon trip due to high temperature. Check ambient temperature and airflow

103

1..80

5

Internal error. A recoverable internal MCU error has occured. Please inform Kraft in which circomstances this error occurs

103

1..80

6


103

1..80

7


103

1..80

8

overload

103

1..80

9

No load detected

103

1..80

10

PDU overtemperature. Check ambient temperature and airflow

103

1..80

11

PSU overtemperature. Check ambient temperature and airflow

103

1..80

12

Overvoltage detected. Check secondary cabling and parameter settings.

103

1..80

13

DC-Link error.